Vacuum Interrupters
TD14-12/2500-40AQ
TD14-12/3150-40BQ
TD14-12/3150-40DQ
Rated parameters of vacuum interrupter
| № |
Parameter item |
Unit |
Value |
| 1 |
Rated voltage |
kV |
12 |
| 2 |
Rated power-frequency withstanding voltage |
kV |
42 |
| 3 |
Rated lighting impulses withstanding voltage |
kV |
75 |
| 4 |
Rated frequency |
Hz |
50 |
| 5 |
Rated current |
A |
2500 3150 |
| 6 |
Rated peak withstanding current |
kA |
100 |
| 7 |
Rated short-time withstanding current |
kA |
40 |
| 8 |
Rated duration of short-circuit |
s |
4 |
| 9 |
Rated short-circuit breaking current |
kA |
40 |
| 10 |
Rated short-circuit making current |
kA |
100 |
| 11 |
Operations of short-circuit breaking current interruption |
Time |
30 |
| 12 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
| 13 |
Rated single capacitor bank breaking current |
A |
630 |
| 14 |
Mechanical life |
Time |
10000 |
Mechanical parameters of vacuum interrupter:
| № |
Parameter item |
Unit |
Value |
| 1 |
Rated contact gap |
mm |
9±1 |
| 2 |
Contact closing force due to bellows and atmosphere |
N |
250±60 |
| 3 |
Counterforce of contact |
N |
340±60 |
| 4 |
Circuit resistance at low limit of rated contact force |
μΩ |
≤15 |
| 5 |
Contact erosion permission length |
mm |
3 |
| 6 |
Moving part weight |
kg |
2.3 ① |
| Note① Type of TD14 -12/2500-40AQ is 2.2 |
Mechanical parameters of Vacuum Interrupters for Circuit Breaker Applications
| № |
Parameter item |
Unit |
Value |
| 1 |
Average breaking speed |
m/s |
1.1±0.2 |
| 2 |
Average closing speed |
m/s |
0.6±0.2 |
| 3 |
Rated operation pressure of contact |
N |
5000±300 |
| 4 |
Bounce duration of contact closing |
ms |
≤2 |
| 5 |
Rebound amplitude of breaking contact |
ms |
Undetermined |
| 6 |
Out of simultaneity of contact closing and opening |
ms |
﹤1 |