TD-12/4000-50BQ Vacuum Interrupters for Circuit Breaker Applications
Rated parameters of vacuum interrupter
| № |
Parameter item |
unit |
value |
| 1 |
Rated voltage |
kV |
12 |
| 2 |
Rated Short-time power-frequency withstanding voltage |
kV |
48 |
| 3 |
Rated lighting impulses withstanding voltage |
kV |
85 |
| 4 |
Rated frequency |
Hz |
50 |
| 5 |
Rated current |
A |
4000 |
| 6 |
Rated peak withstanding current |
kA |
125 |
| 7 |
Rated short-time withstanding current |
kA |
50 |
| 8 |
Rated duration of short-circuit |
s |
4 |
| 9 |
Rated short-circuit breaking current |
kA |
50 |
| 10 |
Rated short-circuit making current |
kA |
125 |
| 11 |
Breaking times of short-circuit current |
Times |
20 |
| 12 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
| 13 |
Rated single capacitor bank breaking current |
A |
630 |
| 14 |
Mechanical life |
Times |
10000 |
Mechanical parameters of vacuum interrupter:
- №
|
- Parameter item
|
- Unit
|
Value |
- 1
|
- Rated contact gap
|
- mm
|
9±1 * |
| 2 |
Contact closing force |
N |
250±60 |
| 3 |
Counterforce of contact |
N |
340±60 |
| 4 |
Circuit resistance at low limit of rated contact force |
μΩ |
≤10 |
| 5 |
Contact erosion permission length |
- mm
|
3 |
| 6 |
- Moving part weight
|
kg |
3.5 |
| *In special conditions the mechanical performance won′t be affected when contact distance is of 6~12mm |
Mechanical parameters of vacuum interrupter for Circuit Breaker Applications
- №
|
- Parameter item
|
- Unit
|
- Value
|
| 1 |
- Average breaking speed
|
m/s |
1.1±0.2 |
| 2 |
Average closing speed |
m/s |
0.6±0.2 |
| 3 |
Rated operation pressure of contact |
N |
7500±500 |
| 4 |
Bounce duration of contact closing |
ms |
≤2 |
| 5 |
Rebound amplitude of breaking contact |
mm |
≤2 |
| 6 |
Out of simultaneity of contact closing and breaking |
ms |
<1 |