Home > Vacuum Interrupters-Circuit Breaker > TD-12/ 3150-40VK Vacuum Interrupters
Vacuum Interrupters-Circuit Breaker

Vacuum Interrupters

TD-12 / 3150-40VK Vacuum Interrupters for Circuit Breaker Applications
Rated parameters of vacuum interrupter
Parameter item Unit Value
1 Rated voltage kV 12
2 Rated power-frequency withstanding voltage kV 42
3 Rated lighting impulses withstanding voltage kV 75
4 Rated frequency Hz 50
5 Rated current A 3150
6 Rated peak withstanding current kA 100
7 Rated short-time withstanding current kA 40
8 Rated duration of short-circuit s 4
9 Rated short-circuit breaking current kA 40
10 Rated short-circuit making current kA 100
11 Breaking times of short-circuit current Time 30
12 Rated operating sequence   O-0.3s-CO-180s-CO
13 Rated single capacitor bank breaking current A 630
14 Mechanical life Time 10000

Mechanical parameters of vacuum interrupter:
  1. Parameter item
  1. Unit
Value
  1. 1
Rated contact gap
  1. mm
9±1
2 Contact closing force due to bellows and atmosphere N 250±60
3 Counterforce of contact N 340±60
4 Circuit resistance at low limit of rated contact force μΩ ≤10
5 Contact erosion permission length
  1. mm
3
6 Moving part weight kg 2

Mechanical parameters of Vacuum Interrupters for Circuit Breaker Applications
  1. Parameter item
  1. Unit
  1. Value
1
  1. Average breaking speed
m/s 1.3±0.2
2 Average closing speed m/s 0.6±0.2
3 Rated operation pressure of contact N 5000±300
4 Bounce duration of contact closing ms ≤2
5 Rebound amplitude of breaking contact mm ≤2
6 Out of simultaneity of contact closing and opening ms <1
Other Products