| № | Parameter item | Unit | Value |
| 1 | Rated voltage | kV | 40.5 |
| 2 | Rated power-frequency withstanding voltage | kV | 95 |
| 3 | Rated lighting impulses withstanding voltage | kV | 185 |
| 4 | Rated frequency | Hz | 50 |
| 5 | Rated current | A | 1600 |
| 6 | Rated peak withstanding current | kA | 80 |
| 7 | Rated short-time withstanding current | kA | 31.5 |
| 8 | Rated duration of short-circuit | s | 4 |
| 9 | Rated short-circuit breaking current | kA | 31.5 |
| 10 | Rated short-circuit making current | kA | 80 |
| 11 | Breaking times of short-circuit current | Time | 20 |
| 12 | Rated operating sequence | | O-0.3s-CO-180s-CO |
| 13 | Rated single capacitor bank breaking current | A | 630 |
| 14 | Mechanical life | Time | 10000 |