Vacuum Interrupters
TD-18/-120AQ Vacuum interrupter
Specifications of Vacuum Interrupter
- №
| - Parameter item
| - Unit
| - Value
|
- 1
| - Rated voltage
| - kV
| - 18
|
- 2
| - Rated frequency
| - Hz
| - 50
|
- 3
| - Rated lighting impulses withstanding voltage (fracture)
| - kV
| - 115
|
- 4
| - Rated short-time power-frequency withstanding voltage (fracture)
| - kV
| - 63
|
- 5
| - Rated current
| - A
| -
|
- 6
| - Rated short-time withstanding current
| - kA
| - 120
|
- 7
| - Rated peak withstanding current
| - kA
| - 329
|
- 8
| - Rated short-circuit breaking current
| - kA
| - 120
|
- 9
| - Rated short-circuit making current
| - kA
| - 329
|
- 10
| - Rated duration of short-circuit
| - s
| - 4
|
- 11
| - Rated operating sequence
| -
|
- 12
| - Breaking times of short-circuit current
| - Time
| - 2
|
- 13
| - Rated out-of-synchronism symmetric breaking current
| - kA
| - 120×(50%)
|
- 14
| Percentage of DC component in rated short-circuit breaking current | - %
| - 76
|
- 15
| - Shelf life
| - a
| - 20
|
- 16
| - Arcing time
| - ms
| - ≤30
|
- 17
| - Mechanical life
| - Time
| - 10000
|
Mechanical parameters of vacuum interrupter:
| № | - Parameter item
| Unit | Value |
| 1 | Rated contact gap | mm | 13±1 |
| 2 | Contact closing force due to bellows and atmosphere | N | 650±100 |
| 3 | Counterforce of contact | N | 700±100 |
| 4 | Circuit resistance at low limit of rated contact force | - μΩ
| - ≤8
|
| 5 | Contact erosion permission length | - mm
| 3 |
| 6 | Moving part weight | kg | 12 |
Mechanical parameters of Vacuum Interrupters for Circuit Breaker Applications
| № | - Parameter item
| Unit | Value |
| 1 | Average breaking speed | m/s | 1.8±0.1 |
| 2 | Average closing speed | m/s | |
| 3 | Rated operation pressure of contact | N | 43000±1000 |
| 4 | Bounce duration of contact closing | ms | ≤2 |
| 5 | Rebound amplitude of breaking contact | mm | ≤1.5 |
| 6 | Out of simultaneity of contact closing and opening | ms | <1 |