Vacuum Interrupters
TD14-12/1250-20BQ TD14-12/1250-25BQ
TD14-12/1250-20DQ TD14-12/1250-25DQ
TD14-12/1250-20FQ TD14-12/1250-25FQ
TD14-12/1250-20HQ TD14-12/1250-25HQ
Vacuum Interrupters for Circuit Breaker Applications
Rated parameters of vacuum interrupter
| № | Parameter item | Unit | Value |
| 1 | Rated voltage | kV | 12 |
| 2 | Rated power-frequency withstanding voltage | kV | 42 |
| 3 | Rated lighting impulses withstanding voltage | kV | 75 |
| 4 | Rated frequency | Hz | 50 |
| 5 | Rated current | A | 1250 |
| 6 | Rated peak withstanding current | kA | 50 | 63 |
| 7 | Rated short-time withstanding current | kA | 20 | 25 |
| 8 | Rated duration of short-circuit | s | 4 |
| 9 | Rated short-circuit breaking current | kA | 20 | 25 |
| 10 | Rated short-circuit making current | kA | 50 | 63 |
| 11 | Breaking times of short-circuit current | Time | 30 |
| 12 | Rated operating sequence | | O-0.3s-CO-180s-CO |
| 13 | Rated single capacitor bank breaking current | A | 630 |
| 14 | Mechanical life | Time | 10000 |
Mechanical parameters of vacuum interrupter:
| № | Parameters | Unit | Value |
| 1 | Rated contact distance | mm | 9±1 |
| 2 | Contact closing force due to bellows and atmosphere | N | 120±50 |
| 3 | Counterforce of contact | N | 180±50 |
| 4 | Circuit resistance at low limit of rated contact force | μΩ | ≤25 |
| 5 | Contact erosion permission length | mm | ﹤3 |
| 6 | Moving part weight | kg | 1.0 ① |
| Note ① TD14-12/1250-20FQ、TD14 -12/1250-25FQ: 1.3 |
Mechanical parameters of Vacuum Interrupters for Circuit Breaker Applications:
| № | Parameter item | Unit | Value |
| 1 | Average breaking speed | m/s | 1.0±0.3 |
| 2 | Average closing speed | m/s | 0.55±0.15 |
| 3 | Rated operation pressure of contact | N | 2000±200 |
| 4 | Bounce duration of contact closing | ms | ≤2 |
| 5 | Rebound amplitude of breaking contact | mm | undetermined |
| 6 | Out of simultaneity of contact closing and opening | ms | ﹤1 |