Vacuum Interrupters
Vacuum Interrupters for Circuit Breaker Applications
Rated parameters required for vacuum interrupters
| № |
Parameter item |
Unit |
Value |
| 1 |
Rated voltage |
kV |
12 |
| 2 |
Rated power-frequency withstanding voltage |
kV |
42* |
| 3 |
Rated lighting impulses withstanding voltage |
kV |
75* |
| 4 |
Rated frequency |
Hz |
50 |
| 5 |
Rated current |
A |
630 |
| 6 |
Rated peak withstanding current |
kA |
50 |
| 7 |
Rated short-time withstanding current |
kA |
20 |
| 8 |
Rated duration of short-circuit |
s |
4 |
| 9 |
Rated short-circuit breaking current |
kA |
20 |
| 10 |
Rated short-circuit making current |
kA |
50 |
| 11 |
Operations of short-circuit breaking current interruption |
Time |
30 |
| 12 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
| 13 |
Rated single capacitor bank breaking current |
A |
400 |
| 14 |
Mechanical life |
Time |
10000 |
| * In transformer oil or equivalent insulation medium |
Mechanical parameters of vacuum interrupter
- №
|
- Parameter item
|
- Unit
|
Value |
- 1
|
Rated contact gap |
- mm
|
9±1 |
| 2 |
Contact closing force due to bellows and atmosphere |
N |
80±50 |
| 3 |
Counterforce of contact |
N |
120±50 |
| 4 |
Circuit resistance at low limit of rated contact force |
μΩ |
≤40 |
| 5 |
Contact erosion permission length |
- mm
|
3 |
| 6 |
Moving part weight |
kg |
0.35 |
Mechanical parameters of Vacuum Interrupters for Circuit Breaker Applications
- №
|
- Parameter item
|
- Unit
|
Value |
- 1
|
Rated contact gap |
- mm
|
9±1 |
| 2 |
Contact closing force due to bellows and atmosphere |
N |
80±50 |
| 3 |
Counterforce of contact |
N |
120±50 |
| 4 |
Circuit resistance at low limit of rated contact force |
μΩ |
≤40 |
| 5 |
Contact erosion permission length |
- mm
|
3 |
| 6 |
Moving part weight |
kg |
0.35 |