Home > Vacuum Interrupters-Load Switch > BD-12/630-12.5 Vacuum Interrupters
Ceramics Vacuum Interrupters-Circuit Breaker

Vacuum Interrupters

BD-12/630-12.5 Ceramics vacuum interrupter
Rated parameters of vacuum interrupter
Parameter item Unit Value
1 Rated voltage kV 12
2 Rated power-frequency withstanding voltage kV 42 ①
3 Rated lighting impulses withstanding voltage kV 75 ①
4 Rated frequency Hz 50
5 Rated current A 630 
6 Rated peak withstanding current kA 31.5
7 Rated short-time withstanding current kA 12.5
8 Rated duration of short-circuit s 4
9 Rated short-circuit breaking current kA 12.5
10 Rated short-circuit making current kA 31.5
11 Breaking times of short-circuit current Time 30
12 Rated operating sequence   O-0.3s-CO-180s-CO
13 Rated single capacitor bank breaking current A 400
14 Mechanical life Time 10000
Note:①Value in transformer oil or equivalent insulation equipment

Mechanical parameters of vacuum interrupter:
Parameter item Unit Value
1 Rated contact gap mm 9±1
2 Contact closing force due to bellows and atmosphere N 100±50
3 Counterforce of contact N 110±50
4 Circuit resistance at low limit of rated contact force μΩ ≤40
5 Contact erosion permission length mm 3
6 Moving part weight kg 0.6

Mechanical parameters of Vacuum Interrupters for Switch Disconnector Applications
Mechanical parameters of vacuum circuit breaker:
Parameter item Unit Value
1 Average breaking speed m/s 1.0±0.2
2 Average closing speed m/s 0.6±0.2
3 Rated operation pressure of contact N 1100±100
4 Bounce duration of contact closing ms ≤2
5 Rebound amplitude of breaking contact mm Undetermined
6 Out of simultaneity of contact closing and opening ms ﹤1