Home > Vacuum Interrupters -Contactor > TJC-12/630- 6.3AQ Vacuum Interrupters
Vacuum Interrupters for Contactor

Vacuum Interrupters

TJC-12/630-6.3AQ Vacuum interrupter
TJC-12/630-6.3BQ Vacuum interrupter
TJC-12/630-6.3CQ Vacuum interrupter

Rated parameters of vacuum interrupter
Parameter item Unit Value
1 Rated voltage kV 12
2 Rated power-frequency withstanding voltage kV 42
3 Rated lighting impulses withstanding voltage kV 75
4 Rated frequency Hz 50
5 Rated current A 630
6 Rated short-time withstanding current kA 6.3
7 Rated duration of short-circuit s 4
8 Rated breaking current, max kA 5
9 Rated breaking current, min A 125
10 Rated making current AC-3 kA 5
AC-4 kA 6.3
11 Limited breaking current kA 6.3
12 Working mode Long-term duty type
13 Types   AC-3 AC-4
14 Electricity endurance AC-3 Times 25×104
AC-4 Times 10×104
15 Mechanical life Times 30×104

Mechanical parameters of vacuum interrupter:
Parameter item Unit Value
1 Rated contact gap mm 6
2 Contact closing force due to bellows and atmosphere N 70±30
3 Counterforce of contact N 110±30
4 Circuit resistance at contact force from atmosphere pressure μΩ ≤150
5 Contact erosion permission length mm ≤3
6 Moving part weight kg 0.3

Mechanical parameters of Vacuum Interrupters for Contactor Applications
Parameter item Unit Value
1 Average breaking speed m/s 0.7±0.3
2 Average closing speed m/s 0.3±0.1
3 Rated operation pressure of contact N 110±10
4 Bounce duration of contact closing ms ≤2
5 Rebound amplitude of breaking contact mm ≤2
6 Out of simultaneity of contact closing and opening ms ≤1
Other Products