| Parameter item | Unit | Value |
| Rated voltage | KV | 40.5 |
| lighting impulses withstanding voltage (peak) | KV | 185 |
| Short-time power-frequency withstanding voltage | KV | 95 |
| Rated frequency | Hz | 50 |
| Rated current | A | 1250-2500 |
| Rated short-time withstanding current | KA | 2531.5 |
| Rated duration of short-circuit | S | 4 |
| Rated peak withstanding current | KA | 6380 |
| Rated short-circuit making current | KA | 6380 |
| Rated short-circuit breaking current | KA | 2531.5 |
| DC component, max | ≤40% | |
| Operations of short-circuit breaking current interruption | Time | 20 |
| Rated single capacitor bank breaking current | A | 400 |
| Rated back-to-back capacitor breaking current | A | 400 |
| Mechanical life | Time | 10000 |
| Rated contact gap | Mm | 20±2 |
| Contact closing force due to bellows and atmosphere | N | 220±40 |
| Counterforce of contact | N | 310±40 |
| Circuit resistance at rated contact force | μΩ | ≤20 |
| Contact erosion permission length | Mm | 3 |
| Moving part weight | Kg | 22.7 |
| Internal gas pressure | Pa | ≤1.3×10-3 |
| Shelf life | Year | 20 |
| Rated operating sequence | 0-0.3s-C0-180s-C0 | |
| Mechanical parameters of vacuum switch | ||
| Average breaking speed | m/s | 1.4-2.0 |
| Average closing speed | m/s | 0.8-1.2 |
| Bounce duration of contact closing | Ms | ≤3 |
| Rebound amplitude of breaking contact | Mm | ≤1.5 |