Home > Vacuum Interrupters Integrated Embedded Poles >
EP12/1600-40 Embedded Poles
J001514TVF Embedded Pole

J001514TVF Embedded Poles

Vacuum Interrupters Integrated Embedded Pole
Parameter item Unit Value
Rated voltage KV 12
Rated current A 1250
Rated frequency Hz 50
Rated short-circuit breaking current KA 31.5
Breaking times of short-circuit current Time 50
Rated short-circuit making current KA 80
Rated peak withstanding current KA 80
Rated short-time withstanding current (4 seconds) KA 31.5
Rated single capacitor bank breaking current A 630
Rated back-to-back capacitor breaking current A 400
Short-time power-frequency withstanding voltage KV 48
lighting impulses withstanding voltage (peak) KV 85
Circuit resistance at rated contact force μΩ ≤20
Mechanical life Time 30000
Contact closing force due to bellows and atmosphere N 120±50
Counterforce at rated contact stroke N 210±50
Contact erosion permission length Mm 3
Shelf life Year 20
Part discharge pC ≤5
Rated operating sequence 0-0.3s-C0-180s-C0
Mechanical data of vacuum switch
Rated contact stroke Mm 9±1
Contact connection stroke Mm 3.5±1
Average breaking speed m/s 1.1±0.2
Average closing speed m/s 0.7±0.2
Rated operation pressure of contact N 3100±200
Bounce duration of contact closing Ms ≤2
Out of simultaneity of contact closing and opening Ms ≤1
Rebound amplitude of breaking contact Mm ≤2
Other Products