| Parameter item |
Unit |
Value |
| Rated voltage |
KV |
12 |
| Rated current |
A |
1600 |
| Rated frequency |
Hz |
50 |
Rated short-circuit breaking current
|
KA |
40 |
| Breaking times of short-circuit current |
Time |
30 |
| Rated short-circuit making current |
KA |
100 |
| Rated peak withstanding current |
KA |
100 |
| Rated short-time withstanding current (4 seconds) |
KA |
40 |
| Rated single capacitor bank breaking current |
A |
630 |
| Rated back-to-back capacitor breaking current |
A |
400 |
| Short-time power-frequency withstanding voltage |
KV |
48 |
| lighting impulses withstanding voltage (peak) |
KV |
85 |
| Circuit resistance at rated contact force |
μΩ |
≤20 |
| Mechanical life |
Time |
20000 |
| Contact closing force due to bellows and atmosphere |
N |
2100±50 |
| Counterforce at rated contact stroke |
N |
350±50 |
| Contact erosion permission length |
Mm |
3 |
| Shelf life |
Year |
20 |
| Part discharge |
pC |
≤5 |
| Rated operating sequence |
0-0.3s-C0-180s-C0 |
| Mechanical data of vacuum switch |
| Rated contact gap |
mm |
9±1 |
| Contact connection stroke |
mm |
4±1 |
| Average breaking speed |
m/s |
1.1±0.2 |
| Average closing speed |
m/s |
0.6±0.2 |
| Rated operation pressure of contact |
N |
4300±300 |
| Bounce duration of contact closing |
ms |
≤2 |
| Out of simultaneity of contact closing and opening |
ms |
≤1 |
| Rebound amplitude of breaking contact |
mm |
≤2 |