| Parameter item | Unit | Value |
| Rated voltage | KV | 12 |
| Rated current | A | 3150 |
| Rated frequency | Hz | 50 |
| Rated short-circuit breaking current | KA | 40 |
| Breaking times of short-circuit current | Time | 30 |
| Rated short-circuit making current | KA | 100 |
| Rated peak withstanding current | KA | 100 |
| Rated short-time withstanding current (4 seconds) | KA | 40 |
| Rated single capacitor bank breaking current | A | 630 |
| Rated back-to-back capacitor breaking current | A | 400 |
| Short-time power-frequency withstanding voltage | KV | 48 |
| lighting impulses withstanding voltage (peak) | KV | 85 |
| Circuit resistance at rated contact force | μΩ | ≤15 |
| Mechanical life | Time | 20000 |
| Contact closing force due to bellows and atmosphere | N | 250±60 |
| Counterforce at rated contact stroke | N | 340±60 |
| Contact erosion permission length | Mm | 3 |
| Shelf life | Year | 20 |
| Part discharge | pC | ≤5 |
| Rated operating sequence | 0-0.3s-C0-180s-C0 | |
| Mechanical parameters of vacuum switch | ||
| Rated contact gap | Mm | 9±1 |
| Contact connection gap | Mm | 4±1 |
| Average breaking speed | m/s | 1.1±0.2 |
| Average closing speed | m/s | 0.6±0.2 |
| Rated operation pressure of contact | N | 4300±300 |
| Bounce duration of contact closing | Ms | ≤2 |
| Out of simultaneity of contact closing and opening | Ms | ≤1 |
| Rebound amplitude of breaking contact | Mm | ≤2 |